EasyManua.ls Logo

Danfoss VLT AutomationDrive FC 360

Danfoss VLT AutomationDrive FC 360
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Option Name Description
[0] None
[1] FC Port
[2] Option A PROFIBUS and PROFINET.
8-03 Control Timeout Time
Default value: 1.0 s Parameter type: Range (0.1 s–6000.0 s)
Setup: 1 setup Conversion index: -1
Data type: Uint16 Change during operation: True
Enter the maximum time expected to pass between the reception of 2 consecutive telegrams. If this time is exceeded, it indicates that
the serial communication has stopped. The function that is selected in parameter 8-04 Control Timeout Function is then carried out.
8-04 Control Timeout Function
Default value: [0] Off Parameter type: Option
Setup: 1 setup Conversion index:
Data type: Uint8 Change during operation: True
Select the timeout function. The timeout function activates when the control word fails to be updated within the time period specified in
parameter 8-03 Control Word Timeout Time.
Option Name Description
[0] Off Resume control via fieldbus (fieldbus or
standard), using the most recent control
word.
[1] Freeze output Freeze output frequency until
communication resumes.
[2] Stop Stop with auto restart until
communication resumes.
[3] Jogging Run the motor at jog frequency until
communication resumes.
[4] Max. speed Run the motor at maximum frequency
until communication resumes.
[5] Stop and trip Stop the motor and trip, then reset the
drive to restart:
Via fieldbus.
Via [Reset].
Via a digital input.
[6] Qstop and trip
[26] Trip
172 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLAutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Related product manuals