Programming Guide | VLT® AutomationDrive FC 360
Option Name Description
[3] Process Closed Loop Enables the use of process control in the
drive. The process control parameters
are set in parameter group 7-2* Process
Ctrl. Feedback and parameter group 7-3*
Process PID Ctrl.
[4] Torque Open Loop Enables the use of torque open loop
in VVC+ mode (parameter 1-01 Motor
Control Principle). The torque PID
parameters are set in parameter group
7-1* Torque PI Control.
[6] Surface Winder Enables the use of surface winder control.
Specific parameters in parameter group
7-2* Process Ctrl. Feedb. and parameter
group 7-3* Process PID Ctrl.
[7] Extended PID Speed OL Enables the use of extended PID speed
OL. Specific parameters in parameter
group 7-2* Process Ctrl. Feedb. to
parameter group 7-5* Ext. Process PID Ctrl.
1-01 Motor Control Principle
Default value: [1] VVC+ Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: False
Select U/f mode, VVC+ mode, or flux mode as motor control principle.
 NOTICE
When parameter 1-10 Motor Construction is set to PM enabled options, only option [0] U/f is not available.
Option Name Description
[0] U/f Used for parallel-connected motors
and/or special motor applications. Set
the U/f settings in parameter 1-55 U/f
Characteristic - U and parameter 1-56 U/f
Characteristic - F.
[1] VVC+ Normal running mode, including slip and
load compensations.
[2] Flux sensorless
[3] Flux w/motor feedb