NOTICE
The option [2] Flux sensorless and [3] Flux w/motor feedb are hidden without flux license activation.
1-03 Torque Characteristics
Default value: [0] Constant torque Parameter type: Option
Setup: All setups Conversion index:
Data type: Uint8 Change during operation: False
Select the torque characteristic required. VT and AEO are both energy-saving operations.
Option Name Description
[0] Constant torque Motor shaft output provides constant
torque under variable speed control.
[1] Variable Torque Motor shaft output provides variable
torque under variable speed control. Set
the variable torque level in parameter
14-40 VT Level.
[2] Auto Energy Optim. CT Automatically optimizes energy
consumption by minimizing
magnetization and frequency via
parameter 14-41 AEO Minimum
Magnetisation.
[5] Constant Power
1-06 Clockwise Direction
Default value: [0] Normal Parameter type: Option
Setup: 1 setup Conversion index:
Data type: Uint8 Change during operation: False
This parameter defines the term clockwise corresponding to the LCP direction arrow. Used for easy change of direction of shaft rotation
without swapping motor wires.
Option Name Description
[0] Normal The motor shaft turns in clockwise
direction when drive is connected to
motor (U to U; V to V; and W to W).
[1] Inverse The motor shaft turns in counterclockwise
direction when drive is connected to
motor (U to U; V to V; and W to W).