Programming Guide | VLT® AutomationDrive FC 360
1-07 Motor Angle Offset Adjust
Default value: [0] Manual Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: False
Select motor angle offset adjustment type.
Option Name Description
[0] Manual Adjustment of parameter 1-41 Motor
Angle Offset is required. Only for absolute
feedback devices.
[1] Auto Adjustment of parameter 1-41 Motor
Angle Offset. For all types of feedback
devices during first start after power-up.
[2] Auto Every Start Same as [1] Auto for every start.
[3] Off Same as [0] Manual for all feedback
devices.
[4] Once with Store Same as [0] Manual for all feedback
devices, but the value in parameter 1-41
Motor Angle Offset will be automatically
updated.
[5] Auto Every Start & Run Same as [2] Auto Every Start but when
output frequency is above parameter
1-53 Model Shift Frequency, the control
switches to open loop angle estimation.
1-08 Motor Control Bandwidth
Default value: Size related Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: False
Select motor control bandwidth type.
Option Name Description
[0] High Suitable for high dynamic response.
[1] Medium Suitable for smooth steady state
operation.
[2] Low Suitable for smooth steady state
operation with lowest dynamic response.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 51