Option Name Description
[13] Below current, low The motor current is lower than set in
parameter 4-50 Warning Current Low.
[14] Above current, high The motor current is higher than set in
parameter 4-51 Warning Current High.
[15] Out of frequency range Output frequency is outside the frequency
range.
[16] Below frequency, low The output speed is lower than the setting
in parameter 4-40 Warning Freq. Low.
[17] Above frequency, high The output speed is higher than the
setting in parameter 4-41 Warning Freq.
High.
[18] Out of feedb. range The feedback is outside the range set in
parameter 4-56 Warning Feedback Low
and parameter 4-57 Warning Feedback
High.
[19] Below feedback, low The feedback is below the limit set in
parameter 4-56 Warning Feedback Low.
[20] Above feedback, high The feedback is above the limit set in
parameter 4-57 Warning Feedback High.
[21] Thermal warning The thermal warning turns on when the
temperature exceeds the limit in the
motor, the drive, the brake resistor, or the
thermistor.
[22] Ready, no thermal warning The drive is ready for operation, and there
is no overtemperature warning.
[23] Remote, ready, no TW The drive is ready for operation
and is in auto-on mode. There is no
overtemperature warning.
[24] Ready, no over-/under voltage The drive is ready for operation and the
mains voltage is within the specified
voltage range (see the Specifications
section in the design guide).
[25] Reverse The motor runs (or is ready to
run) clockwise when logic = 0 and
counterclockwise when logic = 1. The
output changes as soon as the reversing
signal is applied.
[26] Bus OK Active communication (no timeout) via
the serial communication port.
[27] Torque limit & stop Use in performing a coast stop and in
torque limit condition. If the drive has
received a stop signal and is at the torque
limit, the signal is logic 0.
120 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals