6-13 Terminal 53 High Current
Default value: 20.00 mA Parameter type: Range (0.00–20.00 mA)
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
Enter the high current value corresponding to the high reference/feedback set in parameter 6-15 Terminal 53 High Ref./Feedb. Value.
6-14 Terminal 53 Low Ref./Feedb. Value
Default value: 0.000 Parameter type: Range (-4999.000–4999.000)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: True
Enter the reference or feedback value that corresponds to the voltage or current set in parameter 6-10 Terminal 53 Low Voltage to
parameter 6-12 Terminal 53 Low Current.
6-15 Terminal 53 High Ref./Feedb. Value
Default value: Size related Parameter type: Range (-4999.000–4999.000)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: True
Enter the reference or feedback value that corresponds to the voltage or current set in parameter 6-11 Terminal 53 High Voltage to
parameter 6-13 Terminal 53 High Current.
6-16 Terminal 53 Filter Time Constant
Default value: 0.01 s Parameter type: Range (0.01–10.00 s)
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
Enter the time constant. This constant is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal 53. A
high time constant value improves dampening, but also increases the time delay through the filter.
6-19 Terminal 53 mode
Default value: [1] Voltage mode Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Select whether terminal 53 is used for current or voltage input.
Option Name
[0] Current mode
[1] Voltage mode
146 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360