13-41 Logic Rule Operator 1
Default value: [0] Disabled Parameter type: Option, Array [6]
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Select the 1st logical operator to use on the boolean inputs from parameter 13-40 Logic Rule Boolean 1 and parameter 13-42 Logic Rule
Boolean 2.
Option Name Description
[0] Disabled Ignore parameter 13-42 Logic Rule
Boolean 2, parameter 13-43 Logic Rule
Operator 2, and parameter 13-44 Logic
Rule Boolean 3.
[1] AND Evaluate the expression [13-40] AND
[13-42].
[2] OR Evaluate the expression [13-40] OR
[13-42].
[3] AND NOT Evaluate the expression [13-40] AND NOT
[13-42].
[4] OR NOT Evaluate the expression [13-40] OR NOT
[13-42].
[5] NOT AND Evaluate the expression NOT [13-40] AND
[13-42].
[6] NOT OR Evaluate the expression NOT [13-40] OR
[13-42].
[7] NOT AND NOT Evaluate the expression NOT [13-40] AND
NOT [13-42].
[8] NOT OR NOT Evaluate the expression NOT [13-40] OR
NOT [13-42].
13-42 Logic Rule Boolean 2
Default value: [0] False Parameter type: Option, Array [6]
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Select the 2nd boolean (true or false) input for the selected logic rule. See parameter 13-01 Start Event ([0]–[61]) and parameter 13-02
Stop Event ([70]– [74]) for further description.
Option Name
[0] False
[1] True
220 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360