Programming Guide | VLT® AutomationDrive FC 360
Figure 44: Kinetic Back-up Trip
14-11 Mains Fault Voltage Level
Default value: 342 V Parameter type: Range (100–800 V)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
This parameter defines the threshold voltage at which the selected function in parameter 14-10 Mains Failure is activated. Based on the
supply quality, consider selecting 90% of the nominal mains as the detection level. For a supply of 380 V, parameter 14-11 Mains Fault
Voltage Level should be set to 342 V. This results in a DC detection level of 462 V (parameter 14-11 Mains Fault Voltage Level x 1.35).
14-12 Response to Mains Imbalance
Default value: [0] Trip Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Operation under severe mains imbalance conditions reduces the lifetime of the motor. Conditions are considered severe if the motor is
operated continuously near nominal load (for example, a pump or fan running near full speed).
Option Name Description
[0] Trip Trip the drive.
[1] Warning Issue a warning.
[2] Disabled No action is taken.
[3] Derate Derate the drive.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 235