14-30 Current Lim Ctrl, Proportional Gain
Default value: 100% Parameter type: Range (0–500%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Enter the proportional gain value for the current limit controller. Selection of a high value makes the controller react faster. Too high a
setting leads to controller instability.
14-31 Current Lim Ctrl, Integration Time
Default value: Size related Parameter type: Range (0.002–2 s)
Setup: All setups Conversion index: -3
Data type: Uint16 Change during operation: True
Control the current limit control integration time. Setting it to a lower value makes it react faster. A setting too low leads to control
instability.
14-32 Current Lim Ctrl, Filter Time
Default value: 5.0 ms Parameter type: Range (1.0–100.0 ms)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
Set a time constant for the current limit controller low-pass filter.
14-34 Stall Protection Adjustment Factor
Default value: 100% Parameter type: Range (50%–200%)
Setup: All setups Conversion index: 0
Data type: Uint8 Change during operation: True
Define the stall protection adjustment factor.
14-35 Stall Protection
Default value: [1] Enabled Parameter type: Option
Setup: All setups Conversion index:
Data type: Uint8 Change during operation: False
Enable or disable the stall protection function.
Option Name Description
[0] Disabled Disable the stall protection function.
[1] Enabled Enable the stall protection when field
weakening mode and Flux mode are
active.
240 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507