Programming Guide | VLT® AutomationDrive FC 360
Option Name
[0] Absolute
[1] Relative
37-04 Pos. Velocity
Default value: 300 RPM Parameter type: Range (1–30000 RPM), Array
[8]
Setup: 1 setup Conversion index: 0
Data type: Uint16 Change during operation: True
Define the velocity during positioning. The maximum value must not exceed the value specified in parameter 32-80 Maximum Allowed
Velocity.
37-05 Pos. Ramp Up Time
Default value: 5.00 s Parameter type: Range (0.01–600.00 s), Array
[8]
Setup: 1 setup Conversion index: -2
Data type: Uint16 Change during operation: False
It is defined as the time in milliseconds that it takes to ramp from standstill to parameter 32-80 Maximum Allowed Velocity.
37-06 Pos. Ramp Down Time
Default value: 5.00 s Parameter type: Range (0.01–600.00 s), Array
[8]
Setup: 1 setup Conversion index: -2
Data type: Uint16 Change during operation: False
It is defined as the time in milliseconds that it takes to ramp from parameter 32-80 Maximum Allowed Velocity to standstill.
37-07 Pos. Behavior After Reached
Default value: [0] Coast&Brake Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
When the automatic brake control function is disabled, the drive controls the application also at standstill. When the automatic brake
control function is enabled, the mechanical brake is automatically activated every time the application is at standstill for a time period
specified in parameter 37-08 Pos. Hold Delay.
Option Name
[0] Coast & Brake
[1] Zero Speed Hold