Table 25: Warnings and Alarms Code List (continued)
Number Description Warning Alarm Trip lock Cause
52 AMA low I
nom
– X – Motor current is too low. Check the settings.
53 AMA big motor – X – The power size of the motor is too large for the AMA to
operate.
54 AMA small motor – X – The power size of the motor is too small for the AMA to
operate.
55 AMA parameter range – X – The parameter values of the motor are outside of the ac-
ceptable range. AMA does not run.
56 AMA interrupt – X – The AMA is interrupted.
57 AMA timeout – X – –
58 AMA internal – X – Contact the local supplier.
59 Current limit X X – The drive is overloaded.
60 External interlock – X – –
61 Encoder loss X X – –
62 Output Freq limit X X – Refer to the chapter List of Warnings and Alarms.
63 Mechanical brake low – X – Actual motor current has not exceeded release brake
current within start delay time window.
64 Voltage limit X – – The load and speed combination demands a motor volt-
age higher than the actual DC-link voltage.
65 Control card temp X X X The cutout temperature of the control card is 80 °C (176
°F).
67 Option module configu-
ration has changed
– X – One or more options have either been added or re-
moved since the last power-down.
69 Power card temp X X X –
70 Illegal FC config – X X –
80 Drive initialized to de-
fault value
– X – All parameter settings are initialized to default settings.
87 Auto DC brake X – – Occurs in IT mains when the drive coasts and the DC
voltage is higher than 830 V. Energy on DC-link is con-
sumed by the motor. This function can be enabled/dis-
abled in parameter 0-07 Auto DC Braking.
88 Option detection – X – A change in the option layout is detected. Parameter
14-89 Option Detection is set to [0] Frozen configuration
and the option layout has been changed.
• To apply the change, enable option layout changes in
parameter 14-89 Option Detection.
• Alternatively, restore the correct option configuration.
308 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals