Programming Guide | VLT® AutomationDrive FC 360
WARNING/ALARM 17, Control Word Timeout
Cause
There is no communication to the drive. The warning is only active when parameter 8-04 Control Word Timeout Function is NOT set to [0]
Off. If parameter 8-04 Control Word Timeout Function is set to [5] Stop and Trip, a warning appears. The drive then ramps down until it
trips, while giving an alarm. Parameter 8-03 Control Timeout Time could possibly be increased.
Troubleshooting
l Check connections on the serial communication cable.
l Increase parameter 8-03 Control Word Timeout Time.
l Check the operation of the communication equipment.
l Verify a proper installation based on EMC requirements.
ALARM 18, Start Failed
Cause
The speed cannot exceed the value set in parameter 1-78 Compressor Start Max Speed [Hz] during start within the allowed time, which is
set in parameter 1-79 Compressor Start Max Time to Trip. The alarm may be caused by a blocked motor.
Troubleshooting
l Check if the motor is blocked.
l Check if the start max speed is set higher than the working speed after ramp up.
l Check if the start max time to trip is set shorter than the normal ramp up time.
WARNING/ALARM 20, Temp. Input Error
Cause
The temperature detected by VLT® Sensor Input Option MCB 114 exceeds the limit.
This warning/alarm is only active when [5] Stop and trip is selected in parameter 35-06 Temperature Sensor Alarm Function.
Troubleshooting
l Check the settings of the following parameters:
a. parameter group 35-1* Temp. Input X48/4
b. parameter group 35-2* Temp. Input X48/7
c. parameter group 35-3* Temp. Input X48/10
l Check the feedback temperature from the following parameters:
a. parameter 18-37 Temp. Input X48/4
b. parameter 18-38 Temp. Input X48/7
c. parameter 18-39 Temp. Input X48/10
ALARM 22, Hoist Mechanical Brake
Cause
This alarm occurs when the torque reference was not reached before timeout (parameter 2-27 Torque Ramp Up Time).
Troubleshooting
l Check if mechanical brake is broken or opened before start.
l Check if parameter 2-27 Torque Ramp Up Time is too short.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 317

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals