Programming Guide | VLT® AutomationDrive FC 360
WARNING 49, SPEED LIMIT
Cause
The warning is shown when the speed is outside of the specified range in parameter 4-12 Motor Speed Low Limit [Hz] and parameter
4-14 Motor Speed High Limit [Hz].
Troubleshooting
l Check if the system ran outside of the speed range.
l Check if parameter 4-12 Motor Speed Low Limit [Hz] and parameter 4-14 Motor Speed High Limit [Hz] are set correctly..
ALARM 50, AMA Calibration
Cause
A calibration error has occurred.
Troubleshooting
l Contact a Danfoss supplier or the Danfoss service department.
ALARM 51, AMA check U
nom
and I
nom
Cause
The settings for motor voltage, motor current, and motor power are wrong.
Troubleshooting
l Check the settings in parameter 1-20 to parameter 1-25.
ALARM 52, AMA Low I
nom
Cause
The motor current is too low.
Troubleshooting
l Check the setting in parameter 1-24 Motor Current.
ALARM 53, AMA Big Motor
Cause
The power size of the motor is too large for the AMA to operate.
Troubleshooting
l Check the settings in parameter group 1-2* Motor Data.
ALARM 54, AMA Small Motor
Cause
The power size of the motor is too small for the AMA to operate.
Troubleshooting
l Check the settings in parameter group 1-2* Motor Data.