Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select the operating mode after reconnection of the drive to mains voltage after power-down in hand-on mode.
Option Name Description
[0] Resume Restart the drive, maintaining the start/
stop settings (applied by [Hand On/Off])
selected before power-down of the drive.
[1] Forced stop, ref=old Restart the drive with a saved local
reference after mains voltage reappears
and after pressing [Hand On].
[2] Forced stop, ref=0 Reset the local reference to 0 after
restarting the drive.
0-06 GridType
Default value: Size related Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: False
Select the grid type of the supply voltage/frequency.
l IT Grid is a supply mains where there are no connections to ground.
l Delta is a supply mains where the secondary part of the transformer is delta connected and 1 phase is connected to ground.
 NOTICE
Not all options are supported in all power sizes.
Option Name
[10] 380-440V/50Hz/IT-grid
[11] 380-440V/50Hz/Delta
[12] 380-440V/50Hz
[20] 440-480V/50Hz/IT-grid
[21] 440-480V/50Hz/Delta
[22] 440-480V/50Hz
[110] 380-440V/60Hz/IT-grid
[111] 380-440V/60Hz/Delta
[112] 380-440V/60Hz
[120] 440-480V/60Hz/IT-grid
34 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507