Option Name Description
[0] Disabled No function.
[1] Enabled Enable the drive to catch and control a
spinning motor. When parameter 1-73
Flying Start is enabled, parameter 1-71
Start Delayand parameter 1-72 Start
Function have no function.
[2] Enabled Always Enable flying start at every start
command.
[3] Enabled Ref. Dir. Enable the drive to catch and control a
spinning motor. The search is performed
only in the reference direction.
[4] Enab. Always Ref. Dir. Enable flying start at every start
command. The search is performed only
in the reference direction.
[11] v2 Enabled Enable flying start version 2, after coast.
[12] v2 Enabled Always Enable flying start version 2, at every start.
[13] v2 Enabled Ref. Dir. Enable flying start version 2, after coast,
search in reference direction only.
[14] v2 Enab. Alw. Ref. Dir. Enable flying start version 2, ok at every
start, search in reference direction only.
1-75 Start Speed [Hz]
Default value: Size related Parameter type: Range (0.0–500.0 Hz)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
This parameter can be used for hoist applications (cone rotor). Set a motor start speed. After the start signal, the output speed leaps
to the set value. Set the start function in parameter 1-72 Start Function to [3] Start speed cw, [4] Horizontal operation, or [5] VVC+
clockwise, and set a start delay time in parameter 1-71 Start Delay.
1-76 Start Current
Default value: Size related Parameter type: Range (0.00–1000.00 A)
Setup: All setups Conversion index: -2
Data type: Uint32 Change during operation: True
Some motors, for example cone rotor motors, need extra current/starting speed to disengage the rotor. To obtain this boost, set the
required current in this parameter. Set parameter 1-72 Start Function to [3] Start speed cw or [4] Horizontal operation, and set a start
delay time in parameter 1-71 Start Delay.
1-78 Compressor Start Max Speed [Hz]
Default value: 0.0 Hz Parameter type: Range (0.0–500.0 Hz)
72 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360