Programming Guide | VLT® AutomationDrive FC 360
Table 14: Preset Referenece Bits (continued)
Preset ref. bit 2 1 0
Preset ref. 6 1 1 0
Preset ref. 7 1 1 1
3-11 Jog Speed [Hz]
Default value: 5.0 Hz Parameter type: Range (0.0–500.0 Hz)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
The jog speed is a fixed output speed at which the drive runs when the jog function is activated. See also parameter 3-80 Jog Ramp Time.
The jog speed must not exceed the setting in parameter 4-14 Motor Speed High Limit [Hz].
3-12 Catch Up/Slow Down Value
Default value: 0.00% Parameter type: Range (0.00–100.00%)
Setup: All setups Conversion index: -2
Data type: Int16 Change during operation: True
Enter a percentage value to be either added to or deducted from the actual reference for catching up or slowing down respectively. If
[28] Catch up is selected via 1 of the digital inputs (parameter 5-10 Terminal 18 Digital Input to parameter 5-15 Terminal 33 Digital Input),
the percentage value is added to the total reference. If [29] Slow down is selected via 1 of the digital inputs (parameter 5-10 Terminal 18
Digital Input to parameter 5-15 Terminal 33 Digital Input), the percentage value is deducted from the total reference.
3-13 Reference Site
Default value: [0] Linked to Hand/Auto Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select which reference site to activate.
Option Name Description
[0] Linked to Hand/Auto Use the local reference in hand-on mode
or the remote reference in Auto mode.
[1] Remote Use the reference in hand-on mode.
[2] Local Use the reference in Auto mode.
3-14 Preset Relative Reference
Default value: 0.00% Parameter type: Range (-100.00–100.00%)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: True
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 89

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals