Table 14: Preset Referenece Bits (continued)
Preset ref. bit 2 1 0
Preset ref. 6 1 1 0
Preset ref. 7 1 1 1
3-11 Jog Speed [Hz]
Default value: 5.0 Hz Parameter type: Range (0.0–500.0 Hz)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
The jog speed is a fixed output speed at which the drive runs when the jog function is activated. See also parameter 3-80 Jog Ramp Time.
The jog speed must not exceed the setting in parameter 4-14 Motor Speed High Limit [Hz].
3-12 Catch Up/Slow Down Value
Default value: 0.00% Parameter type: Range (0.00–100.00%)
Setup: All setups Conversion index: -2
Data type: Int16 Change during operation: True
Enter a percentage value to be either added to or deducted from the actual reference for catching up or slowing down respectively. If
[28] Catch up is selected via 1 of the digital inputs (parameter 5-10 Terminal 18 Digital Input to parameter 5-15 Terminal 33 Digital Input),
the percentage value is added to the total reference. If [29] Slow down is selected via 1 of the digital inputs (parameter 5-10 Terminal 18
Digital Input to parameter 5-15 Terminal 33 Digital Input), the percentage value is deducted from the total reference.
3-13 Reference Site
Default value: [0] Linked to Hand/Auto Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select which reference site to activate.
Option Name Description
[0] Linked to Hand/Auto Use the local reference in hand-on mode
or the remote reference in Auto mode.
[1] Remote Use the reference in hand-on mode.
[2] Local Use the reference in Auto mode.
3-14 Preset Relative Reference
Default value: 0.00% Parameter type: Range (-100.00–100.00%)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: True