Programming Guide | VLT® AutomationDrive FC 360
3-16 Reference 2 Source
Default value: [2] Analog Input 54 Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select the reference input to be used for the second reference signal. Parameter 3-15 Reference 1 Source, parameter 3-16 Reference 2
Source, and parameter 3-17 Reference 3 Source define up to 3 different reference signals. The sum of these reference signals defines the
actual reference.
Option Name
[0] No function
[1] Analog Input 53
[2] Analog Input 54
[7] Frequency input 29
[8] Frequency input 33
[11] Local bus reference
[20] Digital pot. meter
[32] Bus PCD
3-17 Reference 3 Source
Default value: [11] Local bus reference Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select the reference input to be used for the third reference signal. Parameter 3-15 Reference 1 Source, parameter 3-16 Reference 2
Source, and parameter 3-17 Reference 3 Source define up to 3 different reference signals. The sum of these reference signals defines the
actual reference.
Option Name
[0] No function
[1] Analog Input 53
[2] Analog Input 54
[7] Frequency input 29
[8] Frequency input 33
[11] Local bus reference
[20] Digital pot. meter
[32] Bus PCD