Recommended actions:
Contact the supplier of the drive.
Trip dESt
Value 199
Short description A parameter is being changed by more than 1 routing destination
This trip indicates that destination output parameters of two or more logic functions within the drive are writing to the same parameter.
Recommended actions:
Set Pr mm.000 to "Destinations" or 12001 and check all visible parameters in all menus for parameter write conflicts
Trip Dr.Cf
Value 232
Short description Incorrect configuration data
The power stage hardware does not match the drive configuration data.
Sub-
trip
Reason
1
The power stage hardware does not match the drive configuration data (size 5
and above).
2 The power stage hardware detected is invalid.
3
The power stage hardware does not match the drive configuration data (Sizes 1 -
4)
Recommended actions:
Return the drive to the supplier.
Trip EEF
Value 31
Short description Non-volatile memory failure
This trip indicates that default parameters have been loaded because of one of the reasons given below.
Sub-
trip
Reason
1 The most significant digit of the internal parameter database version number has changed.
2
The CRC’s applied to the parameter data stored in internal non-volatile memory indicate that a valid set of parameters cannot be
loaded.
3
The drive mode restored from internal non-volatile memory is outside the allowed range for the product or the derivative image does
not allow the previous drive mode.
4 The drive derivative image has been changed and it has changed the customisation of the drive core menus.
5 The power stage hardware has been changed and changed the customisation of the drive core menus.
6 Reserved
7 Reserved
8 The control board hardware has been change and changed the customisation of the drive core menus.
9 The checksum on the non-parameter area of the EEPROM has failed.
The drive holds two banks of user save parameters and two banks of power down save parameters in non-volatile memory. If the last bank of either set of parameters that was saved
is corrupted a UserSave or PowerDownSave trip is produced. If one of these trips occurs the parameters values that were last saved successfully are used. It can take some time
to save parameters when requested by the user and if the power is removed from the drive during this process it is possible to corrupt the data in the non-volatile memory.
If both banks of user save parameters or both banks of power down save parameters are corrupted or one of the other conditions given in the table above occurs EEPROMFail.xxx
trip is produced. If this trip occurs it is not possible to use the data that has been saved previously, and so the drive will be loaded with default parameters. The trip can only be reset if
Parametermm.000 (mm.000) is set to 10, 11, 1233 or 1244 or if LoadDefaults (11.043) is set to a non-zero value.
Trip Et
Value 6
Short description External trip generated by the application
External trip is initiated as shown in the table below.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
253