Parameter Range Default Type
06.001 Stop Mode
Coast (0), rp (1), rP.dcI (2), dc I (3),
td.dcI (4), diS (5)
rp (1) RW Txt US
06.002 Limit Switch Stop Mode Stop (0), rp (1) rp (1) RW Txt US
06.003 Supply Loss Mode
diS (0), rP.Stop (1), ridE.th (2),
Lt.Stop (3)
diS (0) RW Txt US
06.004 Start/Stop Logic Select 0 to 6 0 RW Num US
06.006 Injection Braking Level 0.0 to 150.0 % 100.0 % RW Num RA US
06.007 Injection Braking Time 0.0 to 100.0 s 1.0 s RW Num US
06.008 Hold Zero Frequency Off (0) or On (1) Off (0) RW Bit US
06.009 Catch A Spinning Motor
diS (0), Enable (1), Fr.Only (2),
Rv.Only (3)
diS (0) RW Txt US
06.010 Enable Conditions 000000000000 to 111111110111 RO Bin ND NC PT
06.011 Sequencer State Machine Inputs 0000000 to 1111111 RO Bin ND NC PT
06.012 Enable Stop Key Off (0) or On (1) Off (0) RW Bit US
06.013 Enable Auxiliary Key diS (0), Fd.Rv (1), Rev (2) diS (0) RW Txt US
06.014 Disable Auto Reset On Enable Off (0) or On (1) Off (0) RW Bit US
06.015 Drive Enable Off (0) or On (1) On (1) RW Bit US
06.016 Date 00-00-00 to 31-12-99 RW Date ND NC PT
06.017 Time 00:00:00 to 23:59:59 RW Time ND NC PT
06.018 Day Of Week
Sun (0), Non (1), Tue (2), Ued (3),
Thu (4), Fri (5), Sat (6)
RO Txt ND NC PT
06.019 Date/Time Selector
Set (0), Po.up (1), Run (2), Acc.Po (3),
Re.Pad (5), Slot.1 (6)
Po.up (1) RW Txt US
06.020 Date Format Std (0), US (1) Std (0) RW Txt US
06.021 Time Between Filter Changes 0 to 30000 Hours 0 Hours RW Num US
06.022 Filter Change Required / Change Done Off (0) or On (1) RW Bit ND NC
06.023 Time Before Filter Change Due 0 to 30000 Hours RO Num ND NC PT PS
06.024 Reset Energy Meter Off (0) or On (1) Off (0) RW Bit
06.025 Energy Meter: MWh ±999.9 MWh RO Num ND NC PT PS
06.026 Energy Meter: kWh ±99.99 kWh RO Num ND NC PT PS
06.027 Energy Cost Per kWh 0.0 to 600.0 0.0 RW Num US
06.028 Running Cost ±32000 RO Num ND NC PT
06.029 Hardware Enable Off (0) or On (1) RO Bit ND NC PT
06.030 Run Forward Off (0) or On (1) Off (0) RW Bit NC
06.031 Jog Forward Off (0) or On (1) Off (0) RW Bit NC
06.032 Run Reverse Off (0) or On (1) Off (0) RW Bit NC
06.033 Forward/Reverse Off (0) or On (1) Off (0) RW Bit NC
06.034 Run Off (0) or On (1) Off (0) RW Bit NC
06.035 Forward Limit Switch Off (0) or On (1) Off (0) RW Bit NC
06.036 Reverse Limit Switch Off (0) or On (1) Off (0) RW Bit NC
06.037 Jog Reverse Off (0) or On (1) Off (0) RW Bit NC
06.038 User Enable Off (0) or On (1) On (1) RW Bit NC
06.039 Not Stop Off (0) or On (1) Off (0) RW Bit NC
06.040 Enable Sequencer Latching Off (0) or On (1) Off (0) RW Bit US
06.041 Drive Event Flags 00 to 11 00 RW Bin NC
06.042 Control Word 000000000000000 to 111111111111111 000000000000000 RW Bin NC
06.043 Control Word Enable 0 to 1 0 RW Num US
06.045 Cooling Fan control 0 to 5 2 RW Num US
06.047 Input Phase Loss Detection Mode Full (0), RIPPLE (1), diS (2) Full (0) RW Txt US
06.048 Supply Loss Detection Level 0 to VM_SUPPLY_LOSS_LEVEL V
110V drive: 205 V
200V drive: 205 V
400V drive: 410 V
575V drive: 540 V
690V drive: 540 V
RW Num RA US
06.051 Hold Supply Loss Active Off (0) or On (1) Off (0) RW Bit NC
06.052 Motor Pre‑heat Current Magnitude 0 to 100 % 0 % RW Num US
06.058 Output Phase Loss Detection Time 0.5 (0), 1.0 (1), 2.0 (2), 4.0 (3) 0.5 (0) RW Txt US
06.059 Output Phase Loss Detection Enable Off (0) or On (1) Off (0) RW Bit US
06.060 Standby Mode Enable Off (0) or On (1) Off (0) RW Bit US
06.061 Standby Mode Mask 0000 to 1111 0000 RW Bin US
06.071 Slow Rectifier Charge Rate Enable Off (0) or On (1) Off (0) RW Bit US
06.073 Braking IGBT Lower Threshold ±VM_DC_VOLTAGE_SET V
110V drive: 390 V
200V drive: 390 V
400V drive: 780 V
575V drive: 930 V
690V drive: 1120 V
RW Num RA US
110V drive: 390 V