330 Upgrade and Maintenance Manual RX2530 M4
Liquid cooling (LC)
Ê "Switching on the server" on page 66
Ê "Resuming BitLocker functionality" on page 98
12.4.2 Removing a memory module
12.4.2.1 Preliminary steps
Ê "Suspending BitLocker functionality" on page 77
Ê "Shutting down the server" on page 49
Ê "Disconnecting the power cord" on page 50
Ê "Getting access to the component" on page 52
12.4.2.2 Removing a memory module
Ê Pull up the required memory cover(s), see figure 218 on page 312.
Ê Open the required memory cooling unit, see figure 237 on page 329.
Swing the left/right memory cooling unit(s) in the direction of the pump
(see arrows).
Swing the central memory cooling unit in the direction of the arrow.
Ê If applicable, remove the memory spacers.
Ê Remove the memory module, see section "Removing a memory module" on
page 284.
Ê If applicable, install the memory spacers, see section "Installing a memory
spacer" on page 332.
Ê Close the required memory cooling unit(s).
Ê Position the memory cover(s) over the memory modules and press them
carefully down, see figure 232 on page 323.
Upgrade and Repair Unit
(URU)
Hardware: 5 minutes
Tools: Phillips PH2 / (+) No. 2 screw driver (for the riser module)