F-6 F650 Digital Bay Controller GE Multilin
F.1 FACTORY DEFAULT CONFIGURATION APPENDIX F 
F
SETPOINT > SYSTEM SETUP > GENERAL SETTINGS
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER 
VALUE
Phase CT ratio Phase CT Ratio 1.0 0.1 [1.0 : 6000.0]
Ground CT ratio Ground CT Ratio 1.0 0.1 [1.0 : 6000.0]
Sensitive ground CT ratio Stv Ground CT Ratio 1.0 0.1 [1.0 : 6000.0]
Phase VT ratio Phase VT Ratio 1.0 0.1 [1.0 : 6000.0]
Phase VT connection Phase VT Connection WYE N/A [WYE – DELTA]
Rated voltage Nominal Voltage 100.0 0.1 [1.0 : 250.0]
Rated Frequency Nominal Frequency 50 Hz Hz [50-60]
Phase rotation Phase Rotation ABC N/A [ABC – ACB]
Frequency reference Frequency Reference VI N/A [VI-VII-VIII]
Auxiliary Voltage Auxiliary Voltage VX N/A [VX – VN]
Snapshot Event generation Snapshot Events DISABLED N/A [DISABLED – ENABLED]
SETPOINT > SYSTEM SETUP > FLEX CURVES
FLEX CURVES A > FLEX CURVES B> FLEX CURVES C > FLEX CURVES D
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER 
VALUE
Values for reset points 0.00 pkp Time 0.00xPKP [RST] 0.000 0.001 s [0.000 : 65.535]
Values for reset points 0.05 pkp Time 0.05xPKP [RST] 0.000 0.001 s [0.000 : 65.535]
… … … 0.001 s [0.000 : 65.535]
Values for reset points 0.97 pkp Time 0.97xPKP [RST] 0.000 0.001 s [0.000 : 65.535]
Values for reset points 0.98 pkp Time 0.98xPKP [RST] 0.000 0.001 s [0.000 : 65.535]
Values for operation points 1.03 pkp Time 1.03xPKP [OP] 0.000 0.001 s [0.000 : 65.535]
Values for operation points 1.05 pkp Time 1.05xPKP [OP] 0.000 0.001 s [0.000 : 65.535]
… … … 0.001 s [0.000 : 65.535]
Values for operation points 19.50 pkp Time 19.50xPKP [OP] 0.000 0.001 s [0.000 : 65.535]
Values for operation points 20.00 pkp Time 20.00xPKP [OP] 0.000 0.001 s [0.000 : 65.535]