1.1 Periodic Inspection
C1-3
ME0384-4A
Maintenance Section
Chapter 1 Maintenance and Inspection
No.
Inspection
items
Inspection details
Judgment
criteria
Countermeasures
4
Connection
status
Wiring connectors
loose? (motor/encoder
cable, field network
cable, stop circuit, etc.)
No looseness
Insert until the lock engages.
Wiring cable frayed?
No visual
abnormalities
Check visually and replace the cable.
5
Absolute
battery
Simple absolute unit's
absolute battery (AB-7)
beyond expiry date or
lifespan?
The expiry date is
3 years and
should not
exceed the date
written on a
sticker adhered to
the battery body
Even if the absolute battery is free of
errors, replace it if the expiry date has
passed.
Refer to “Specifications Section
Chapter 7, 7.4 General Specifications
[How to
Replace Absolute Battery]” for
how to make replacement.
6
Preventive/
predictive
maintenan
ce function
Preventive/predictive
maintenance alarms
generated?
No alarm
generated
Refer to "1.4 Preventive Maintenance
Function" and "1.5 Predictive
Maintenance Function" for
countermeasures.