EasyManua.ls Logo

ICON A5 - Page 168

ICON A5
836 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-40 ELECTRICAL SYSTEM / BATTERY
ICON A5 / MAINTENANCE MANUAL CHANGE C2
CHAPTER 6
WARNING: Do NOT jump start the aircraft battery.
9. Continue charging for four more hours after the charge current drops to 1.2 amperes. See Table
6-2 for state of charge (SOC). Turn off charging unit once charging is complete.
Tab l e 6 - 2 : Battery Charging Status Reference
10. Remove negative charging clamps from the aircraft battery charging terminals.
11. Remove positive charging clamps from the aircraft battery charging terminals.
12. Use a multimeter to verify that the battery voltage is at or above 12.6 VDC.
13. Replace the red and black terminal caps. (See Figure 6-3.)
VERIFICATION METHOD:
Turn the master switch ON. Verify that the BATTERY indicator does not stay lit in the annunciator
panel.
NOTE: If the battery requires charging after normal aircraft operation, the
battery may be faulty and must be replaced. See “Battery Diag-
nostic” on page 6-32.
Open Circuit Voltage (VDC) SOC(%)
12.9 or above 100
12.6 75
12.3 50
12.0 25
11.7 or below 0
Source: Concord RG Series Aircraft Battery Owner/Operator Manual (5-0324 Rev D)

Table of Contents

Other manuals for ICON A5