Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Event Correlations: Configuring an Event Correlation
14-7
To configure the alarm table entry for the open door correlation:
1. At the main prompt, configure the alarm entry name
dooropen:
config alarm-entry dooropen
2. Configure the alarm entry dooropen with the following parameters:
event originator correlation DoorAlarms
event type true
event severity major
alarm message Door is open
config alarm-entry dooropen event correlation DoorAlarms true
major Door is open
3. Configure the alarm entry dooropen with the following parameters:
event originator correlation DoorAlarms
event type false
event severity normal
alarm message Door is closed
config alarm-entry dooropen event correlation DoorAlarms false
normal Door is closed
4. Save the configuration.
Note: For an example of configuring an event correlation using a measurement, see
section
Configuring a Measurement Table Entry for State Transitions and
Durations in Chapter 16: Configuring Measurements and the Measurement
Table.