Remote RMX-3200 Version 5.2x Configuration Guide
Configuring the Peripheral Management Subsystem: Configuring Alarms for an Expansion Peripheral
25-17
Configuring Alarms for an Expansion Peripheral
Alarms configured for expansion peripheral I/O points are set up the same way as
alarms configured for on-board Remote RMX-3200 I/O points—the same commands
are used.
To configure alarms for an expansion peripheral:
1. Configure alarm entry
serConnDown as a major alarm that signals when serial
controller
3/5 goes down:
config alarm-entry serConnDown event serial 3/5 down major Serial
controller 3/5 is down
2. Configure alarm entry serConnUp as a normal alarm that signals when serial
controller
3/5 comes up:
config alarm-entry serConnUp event serial 3/5 up normal Serial
controller 3/5 is up
In this scenario, you will:
Configure an alarm entry that signals when a serial connection on a peripheral
unit goes down
Configure an alarm entry that signals when the serial connection comes back
up