Remote RMX-3200 Version 5.2x Configuration Guide
Configuring TBOS Settings: Configuring the TBOS “Points All” Method
21-10
Configuring the TBOS “Points All” Method
To configure the TBOS “points all” method:
1. Enter the following command to configure all points for
display 2 on port serial
5:
config tbos port serial 5 display 2 points all
2. Verify that the TBOS display has been configured properly:
show tbos port serial 5 display 2
The command response displays the default poll states, severity levels and alarm
messages for all points on
display 2:
Note: Execute command show alarm-entries to display all alarm entries that
correspond to the configured points.
3. Save the configuration.
In this scenario, you will configure the TBOS “points all” method for a display. The
“points all” method configures generic default values for all points on a TBOS
display, as well as all corresponding alarm entries.
(Dub)>show tbos port serial 5 display 2
State: enabled
Description:
TL1NE:
Substitution1 Key:
Substitution1 Value:
Substitution2 Key:
Substitution2 Value:
Point Poll State Severity Alarm Message
------------------------------------------------------------------
1 enabled major tbos_5_2 1 In Alarm
2 enabled major tbos_5_2 2 In Alarm
3 enabled major tbos_5_2 3 In Alarm
4 enabled major tbos_5_2 4 In Alarm
5 enabled major tbos_5_2 5 In Alarm
6 enabled major tbos_5_2 6 In Alarm
7 enabled major tbos_5_2 7 In Alarm
8 enabled major tbos_5_2 8 In Alarm
9 enabled major tbos_5_2 9 In Alarm
10 enabled major tbos_5_2 10 In Alarm
11 enabled major tbos_5_2 11 In Alarm
--More--