Remote RMX-3200 Version 5.2x Configuration Guide
Configuring TBOS Settings: Configuring an Equipment Type for a TBOS Display
21-9
4. Enable polling on display 1 and serial 1:
config tbos port serial 1 display 1 enable
config tbos port serial 1 enable
5. Enable SNMP traps in the central alarm table:
config alarm-entry * trap enable
6. Verify that the equipment type for the TBOS display has been configured
properly:
show tbos port serial 1 display 1
The command response displays the default poll states, severity levels and alarm
messages for all points on
display 1:
7. Save the configuration.
(Dub)>show tbos port serial 1 display 1
State: enabled
Description:
TL1NE: 2
Substitution1 Key: farend
Substitution1 Value: florida
Substitution2 Key: nearend
Substitution2 Value: ohio
Category: TBOS-points
NE Name: Alcatel MDR-6000
Point Poll State Severity Alarm Message
------------------------------------------------------------------
1 enabled minor A COMMON LOSS ALM
2 enabled minor A PWR SUPPLY
3 enabled major A RF XMT PWR ALM
4 disabled
5 disabled
6 enabled major A ATPC High Pwr
7 enabled major A DS1 Mux Fail
8 enabled major Alarm A DS1 Input
9 enabled minor B COMMON LOSS ALM
10 enabled minor B PWR SUPPLY
11 enabled major B RF XMT PWR ALM
--More--