Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Measurements and the Measurement Table: Configuring an Alarm Entry for a Measurement
16-7
Configuring an Alarm Entry for a Measurement
To configure the measurement alarm entry:
1. At the main prompt, configure alarm entry
ExtTemp with description External
temperature alarm:
config alarm-entry ExtTemp description External temperature alarm
2. Configure category name envAlms:
config alarm-entry ExtTemp category envAlms
3. Configure network element name sensorUnit:
config alarm-entry ExtTemp ne-name sensorUnit
4. Enable SNMP trap alarm protocol support with priority normal:
config alarm-entry ExtTemp trap enable
config alarm-entry ExtTemp trap priority normal
5. Configure an event for alarm entry ExtTemp with the following settings:
Event originator measurement ExtTemp1
Event trigger high
Event severity level major
Alarm event message $(value).
Note: Keyword $(value) is replaced with the current measurement value.
config alarm-entry ExtTemp event measurement ExtTemp1 high major
$(value)
In this scenario, you will:
Configure an alarm entry description and category
Configure the network element name associated with this alarm entry
Configure SNMP trap alarm protocol support
Configure different alarm actions that occur when a measurement is normal,
low, high, falls below the measurable range, or rises above the measurable
range