Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Measurements and the Measurement Table: Configuring an Alarm Entry for a Measurement
16-8
6. Configure an event for alarm entry ExtTemp with the following settings:
Event originator measurement ExtTemp1
Event trigger low
Event severity level major
Alarm event message $(value).
config alarm-entry ExtTemp event measurement ExtTemp1 low major
$(value)
7. Configure an event for alarm entry ExtTemp with the following settings:
Event originator measurement ExtTemp1
Event trigger in-band
Event severity level normal
Alarm event message $(value).
config alarm-entry ExtTemp event measurement ExtTemp1 in-band
normal $(value)
8. Configure an event for alarm entry ExtTemp with the following settings:
Event originator measurement ExtTemp1
Event trigger input-saturated
Event severity level critical
Alarm event message Input saturated.
config alarm-entry ExtTemp event measurement ExtTemp1 input-
saturated critical Input saturated
9. Configure an event for alarm entry ExtTemp with the following settings:
Event originator measurement ExtTemp1
Event trigger loss-of-signal
Event severity level critical
Alarm event message Signal loss.
config alarm-entry ExtTemp event measurement ExtTemp1 loss-of-
signal critical Signal loss