Remote RMX-3200 Version 5.2x Configuration Guide
Configuring TBOS Settings: Configuring TBOS Polling Settings
21-7
Configuring TBOS Polling Settings
To configure TBOS polling settings on TBOS port serial 1:
1. At the main prompt, set to
8 seconds the amount of time that Remote RMX-3200
waits between receiving a response and sending the next poll:
config tbos port serial 1 poll-delay 80
Note: The entered poll delay time is in tenths of seconds.
2. Set to 12 seconds the amount of time Remote RMX-3200 waits for a response
before moving on to the next poll:
config tbos port serial 1 response-timeout 120
Note: The entered response timeout is in tenths of seconds.
3. Enable the discarding and logging of responses that are received too soon after a
TBOS poll:
config tbos port serial 1 timed-response enable
4. Verify that the TBOS polling settings have been configured properly:
show tbos port serial 1
The command response similar to the following displays:
In this scenario, you will configure the settings for TBOS polling.
(Dub)>show tbos port serial 1
State: disabled
Description:
Poll-delay: 80 (tenths of secs)
Respose-timeout: 120 (tenths of secs)
Timed-response: enabled
Cut-Through:
IP Port: 1
State: disabled
Display Poll State Equipment Type Description
------------------------------------------------------------------
1 disabled none
2 disabled none
3 disabled none
4 disabled none
5 disabled none
6 disabled none
7 disabled none
8 disabled none
--More--
(Dub)>