Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Alarm Entries in the Central Alarm Table: Configuring an Alarm Entry for a Temperature
Sensor
15-4
Configuring an Alarm Entry for a Temperature Sensor
To configure the temperature sensor alarm entry:
1. At the main prompt, configure description
Temperature sensor:
config alarm-entry tempSensor description Temperature sensor
2. Configure category name envAlms:
config alarm-entry tempSensor category envAlms
3. Enable SNMP trap support:
config alarm-entry tempSensor trap enable
4. Configure the SNMP trap priority level to high:
config alarm-entry tempSensor trap priority high
5. Configure the interval at which the alarm entry sends its state information to 5
seconds when the alarm state is
critical:
config alarm-entry tempSensor nagging 5 critical
6. Configure network element name sensorUnit:
config alarm-entry tempSensor ne-name sensorUnit
In this scenario, you will:
Configure an alarm entry description
Configure a category name
Configure SNMP trap support
Configure the interval at which the alarm will send its state
Configure a network element name
Configure the alarm actions that signal when the detected temperature has
exceeded a maximum threshold, passed below a minimum threshold, or
entered into an acceptable range.
Important: This scenario does not show how to configure the analog input that is
associated with the alarm entry. For information on configuring analog
inputs, refer to command
config discrete analog in the Remote
RMX-3200 Command Reference Guide.