Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Modules: Configuring Modules Using Command Line Interface
24-5
The command line response “State” column shall display that Environmental
Monitoring has been enabled.
4. Applications can be disabled by using the above command with “disable” instead
of “enable.”
Realizing and Configuring Network Elements
To realize and configure NEs:
1. Select type
RMBTemperature for Network Element indoorTemperature:
config site network-element indoorTemperature type RMBTemperature
2. In this example, the RMB at this site has already been configured as peripheral 2.
To customize the module with this data, set the value of parameter
peripheralNumber to 2:
config site network-element indoorTemperature param
peripheralNumber 2
3. Configure thresholds for the high temperature alarm and the low temperature
alarm by setting the values of the parameters highTemperature and
lowTemperature:
config site network-element indoorTemperature param
highTemperature 100
config site network-element indoorTemperature param lowTemperature
50
4. Select type RMBHumidity for Network Element indoorHumidity:
config site network-element indoorHumidity type RMBHumidity
5. In this example, the RMB at this site has already been configured as peripheral 2.
To customize the module with this data, set the value of parameter
peripheralNumber to 2:
config site network-element indoorHumidity param peripheralNumber
2
In this scenario, you will:
Realize the indoorTemperature Network Element (NE) and configure
several parameter values
Realize the indoorHumidity NE and configure a parameter value
Show the NEs