Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Modules: Configuring Modules Using Command Line Interface
24-6
6. Verify that the network elements are in the ‘online’ state:
show site network-elements
The command response similar to the following displays:
7. (optional) Display the details of the NE that includes the list of parameters:
show site network-elements indoorTemperature
The command response similar to the following displays:
(Dub)>show site network-elements
Network Element Category Type State
------------------------------------------------------------------------------
backhaulSender BackhaulSender offline
indoorHumidity HumiditySensor RMBHumidity online
indoorTemperature TemperatureSensor RMBTemperature online
monitor ModuleMonitor offline
outdoorHumidity HumiditySensor offline
outdoorTemperatur TemperatureSensor offline
smokeDetector SmokeDetector offline
(Dub)>show site network-elements indoorTemperature
Name - indoorTemperature
Description - Main indoor temperature sensor
Category - TemperatureSensor
Type - RMBTemperature
State - online
InternalState - Online
Parameters
------------------------------------------------------------------------------
Name - REF_temperatureUnits
Value - F
Type - reference
Description - Referenced from temperatureUnits. Per-NE configuration of units
is not supported.
Name - highTemperature
Value - 100 (configured)
Type - reference
Description - High Temperature Alarming Point
Name - lowTemperature
Value - 50
Type - reference
Description - Low Temperature Alarming Point
Name - peripheralNumber
Value - 2 (configured)
Type - integer (1 - 12)
Description - Peripheral number for RMB