Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Alarm Entries in the Central Alarm Table: Configuring an Alarm Entry for a Power Supply
Failure
15-14
Configuring an Alarm Entry for a Power Supply Failure
To configure an alarm entry for a power supply failure:
1. At the main prompt, configure description
5 volt power supply failure:
config alarm-entry powerFail5 description 5 volt power supply
failure
2. Enable tl1 alarm protocol support and set the TL1 alarm class to eqpt
(equipment) and the TL1 service state to
sa (service-affecting):
config alarm-entry powerFail5 tl1 enable
config alarm-entry powerFail5 tl1 eqpt
config alarm-entry powerFail5 tl1 sa
Note: For information on configuring the TL1 NE and TL1 MUX that monitor the
alarm, refer to
Chapter 18: Configuring and Connecting TL1
Infrastructure.
3. Configure an event for alarm entry powerFail5 with the following settings:
Event originator system
Event trigger power-fail-5
Event severity level critical
Alarm event message 5 volt power supply failure.
config alarm-entry powerFail5 event system power-fail-5 critical 5
volt power supply failure
In this scenario, you will:
Configure an alarm entry description
Configure TL1 alarm protocol support
Configure an alarm action that signals that a power supply failure has occurred.