Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Alarm Entries in the Central Alarm Table: Configuring an Alarm Entry for a Power Supply
Failure
15-15
4. (optional) Verify that the alarm entry has been configured properly:
show alarm-entries name powerFail5
The command response appears similar to the following:
5. Save the configuration.
(Dub)>show alarm-entries name powerFail5
Name - powerFail5
State - normal
Current Message -
Description - 5 volt power supply failure
Nagging Interval - 0
Nagging Level - major
Trap - enabled
Raw - disabled
TL1 - enabled
TL1 AID -
TL1 Class - eqpt
TL1 Affect - sa
TL1 Type -
TL1NE - 1
Category -
NE Name -
Alarm Actions:
Severity Originator Trigger Message
------------------------------------------------------------------
critical system power-fail 5 volt power supply
(Dub)>