Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Alarm Entries in the Central Alarm Table: Testing Alarm Table Configurations
15-20
Testing Alarm Table Configurations
After you configure alarm table entries, you can simulate test traps from the alarm
table to test your alarm table configurations before actual alarm traps are sent. Test
mode traps are sent to the management station.
To simulate a test trap from the Remote alarm table:
1. Simulate a test trap with a
normal state for 5 minutes for alarm entry
GPS_Failure:
diag test alarm-entry GPS_Failure mode normal 5
2. (optional) Verify that the GPS_Failure alarm entry is being simulated:
show test alarm-entries
This command response displays the alarm entries that are currently being
simulated (in test mode).
In this scenario, you will simulate a test trap from Remote for a specific alarm entry.
(Dub)>show
(Dub) show>test
(Dub) show test> alarm-entries
Name State Current alarm message
----------------------------------------------------------------------
Explosive_Gas normal Explosive Gas Not Detected
GPS_Failure normal GPS Normal
Generator_OilPressur normal ---
NewTest normal ---
Toxic_Gas normal ---
(Dub) show test