Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Alarm Entries in the Central Alarm Table: Configuring an Alarm Entry for a Discrete Input
15-9
4. Configure an event for alarm entry input0_1 with the following settings:
Event originator input 0/1
Event trigger close
Event severity level major
Alarm event message Light on.
config alarm-entry input0_1 event input 0/1 close major Light on
5. (optional) Verify that the alarm entry has been configured properly:
show alarm-entries name input0_1
The command response appears similar to the following:
6. Save the configuration.
(Dub)>show alarm-entries name input0_1
Name - input0_1
State - normal
Current Message -
Description - Light Switch
Nagging Interval - 0
Nagging Level - major
Trap - enabled
Raw - disabled
TL1 - enabled
TL1 AID -
TL1 Class - eqpt
TL1 Affect - sa
TL1 Type -
TL1NE - 1
Category -
NE Name -
Alarm Actions:
Severity Originator Trigger Message
------------------------------------------------------------------
major input 0/1 open Light off
major input 0/1 close Light on
(Dub)>