Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Alarm Entries in the Central Alarm Table: Configuring an Alarm Entry for a TCP Connection
that Goes Down
15-17
4. (optional) Verify that the alarm entry has been configured properly:
show alarm-entries name TCPConnDown
The command response appears similar to the following:
5. Save the configuration.
(Dub)>show alarm-entries name TCPConnDown
Name - TCPConnDown
State - normal
Current Message -
Description - TCP connection down
Nagging Interval - 0
Nagging Level - major
Trap - enabled
Raw - disabled
TL1 - disabled
TL1 AID -
TL1 Class - env
TL1 Affect - nsa
TL1 Type -
TL1NE - 1
Category -
NE Name -
Alarm Actions:
Severity Originator Trigger Message
------------------------------------------------------------------
major tcp 192.168.0.12 conn-down TCP connection down
(Dub)>