Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Measurements and the Measurement Table: Configuring an Event Correlation for a
Measurement
16-13
To configure the alarm table entry for the fire danger correlation:
1. At the main prompt, configure the alarm entry name
dooropen:
config alarm-entry fireDanger
2. Configure the alarm entry dooropen with the following parameters:
event originator correlation FireDanger
event type true
event severity critical
alarm message Fire alarm exists
config alarm-entry fireDanger event correlation FireDanger true
critical Fire alarm exists
3. Configure the alarm entry doorclosed with the following parameters:
event originator correlation FireDanger
event type false
event severity normal
alarm message Fire alarm is cleared
config alarm-entry dooropen event correlation FireDanger false
normal Fire alarm is cleared
4. Save the configuration.