Engineering via SICAM TOOLBOX II
116 SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
4.1.8.4 Telecontrol Function
4.1.8.4.1 System-Technical Configuration
You can initiate the documentation of the system-technical configuration in the menu
System technique , via the context menu of an automation unit or of a specific system ele-
ment.
The output takes place as a spreadsheet, optionally as preview on the screen or to a printer.
4.1.8.4.2 Process-Technical Settings
You can initiate the documentation of the process-technical settings in the tree of the menu
Edit image , via the context menu of a selected hierarchical level.
The output takes place as a spreadsheet, optionally as preview on the screen or to a printer.
4.1.9 Commissioning and Test
For commissioning and test of the projected settings the following functions are available
(online):
• Load engineering data
• Parameter comparison
• Test functions
• Diagnosis (see section 6.3.2, SICAM TOOLBOX II)
For these functions the engineering PC must be connected with the target device (see 3.7.1,
SICAM TOOLBOX II).
4.1.9.1 Loading Engineering Data
The loading of the parameters of a process-technical plant from the PC into the target device
takes place with the tool “Load Parameters”. You can launch it from the “OPM II” via the menu
Target systems | SICAM 1703 | Parameter loader , or directly via the start menu of
your PC.
With the tool “Parameter Loader” you can add and select automation units, and initiate the
loading via the menu Load | Selected Aus .
All settings that have been performed in the SICAM TOOLBOX II are thereby saved jointly on
the SD card of the target device:
• Configuration parameters
• System-technical parameters
• Process-technical parameters (if they have been transformed previously)
• Application program (if code has been generated previously)