SICAM RTUs, User Manual SICAM CMIC 397
DC8-001-2.09, Edition 08.2016
F.2 SICAM CMIC as Telecontrol Substation with Node Func-
tion (Protocol Converter)
Features:
Communication with the control system via IEC 60870-104
(Ethernet-Interface, X1 or X4, can be set with parameter)
Communication with the protective devices via IEC 61850
(Ethernet-Interface, X1 or X4, can be set with parameter)
2 IP addresses
2 logically separated subnets
Communication only visible on the LAN within the subnet
Data exchange between subnets only via SICAM CMIC application function
1 default router
Parameter Network settings | IP adress | Mode of Ethernet Ports = 2 IP
addresses (independent ports)
Both ethernet-Interfaces (X1, X4) have the same MAC-address
Note
The two integrated ethernet interfaces may not be connected to the same switch/router.
Cause: Both ethernet-Interfaces have the same MAC-address (even with different IP-addresses). -> Prob-
lems with lookup-table management in switch/router.
Substation Zone
Office Zone
Control Center Zone
SICAM CMIC
X4
X1
Router
Control Center
IP-address: 172.17.0.22
Subnet mask: 255.255.0.0
PREx / ET84
IP-address: 172.16.0.3
Subnet mask: 255.255.0.0
Default router: 172.16.0.254
PREx / ET83
IP-address: 192.168.1.130
Subnet mask: 255.255.255.0
Default router: 172.16.0.254
IP-address: 172.16.0.254
IP-address: 192.168.1.n