Engineering via SICAM WEB
152 SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
5.1.4.3 Peripheral Element
In SICAM CMIC you can equip 1 peripheral element. The hardware for the peripheral element
as well as 2 internal I/O modules are integrated on the master control element.
With use of external I/O modules, these must be connected (mechanically) to the target de-
vice before the engineering in SICAM WEB.
The selection of the peripheral element resides in the directory tree also under
SICAM CMIC | Master module | I/O Master module.
In order to configure a peripheral element, select the desired firmware:
USIO80: operation with SICAM TM I/O modules
USIO81: operation with SICAM I/O modules
After the selection of the peripheral element a notification appears:
This means, a new peripheral element (firmware revision) can be accepted only if no signals
are assigned to the peripheral element and to I/O modules. If occasion arises, the correspond-
ing signal assignments must be deleted (see 5.1.9.3, Assigning Signals to the Peripheral Ele-
ment (I/O Master Module) and 5.1.9.4, Assigning Signals to the I/O Module).
Click on the button in order to close the dialog
After the selection of the peripheral element and acceptance with a restart of the target
device is required. Thereby, the target device automatically detects the internal and the con-
nected external I/O modules. Hence, for the equipment of an I/O module you need not make a
selection.