Engineering via SICAM WEB
176 SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
5.1.9.2.2 Parameters with Assignment on the Master Control Module
This data can be changed – for each category – in the table for the signal generation:
Category Parameter Meaning
Communication control
message
Control_function_(COM)
Revision function
Test function
Block function
PRE Protocol element
Station_(COM) Station number (selective 0…99 or all)
CASDU1_(COM) Address of the datapoint. The complete ad-
dress consists of CASDU1, CASDU2, IOA1,
IOA2 and IOA3. CASDU1 and CASDU2 =
255 means no spontaneous transmission.
CASDU2_(COM) Address of the datapoint. The complete ad-
dress consists of CASDU1, CASDU2, IOA1,
IOA2 and IOA3. CASDU1 and CASDU2 =
255 means no spontaneous transmission.
Function_group_(COM) Function group number (0…255)
QID-BSE Source identification basic system element
QID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
QID-SSE Source identification supplementary system
element
Decentral archiving Function_(DEAR)
Archive data
Address main directory
Address subdirectory
Address file
QID-BSE Source identification basic system element
QID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
QID-SSE Source identification supplementary system
element
Error message detailed
diagnostics table
SSE Supplementary system element
Diagnostic_class In case of "all bits, all records, all classes" the
parameter "diagnostic record" and "diagnostic
bit" are not significant
Diagnostic_record Diagnostic record 0…254 = record number
whitin the selected diagnostic class
255 = sum of all bits of all records (the pa-
rameter "diagnostic bit" is not significant)
Diagnostic_bit Bit number (0…15; all bits)
Error message sum diag-
nostics table
Error_location/BSE Error location/basic system element
Error_location/SSE Error location /supplementary system ele-
ment
Error type Error class in the diagnosis
Parameter of measured
values ACP1703
Kind_of_parameter
According NUC
Threshold value
Smoothing factor
Lower limit for transmission of measured
values
Upper limit for transmission of measured
values
Activation parameters for measured values
Interrogation-group General interrogation (group 1…16; none)