C.4 MEMOBUS/Modbus Setup Parameters
552 YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
H5-11: Communications Enter Function Selection
Selects if an Enter command is needed to change parameter values via MEMOBUS/Modbus communications. Refer to
Enter Command on page 571.
Setting 0: Parameter changes applied and saved in drive on Enter command input
Parameter changes are applied on Enter command input and saved in EEPROM in the drive if 0900H in the Enter
command is set to 0. Input the Enter command only after completion of all of the parameter changes.
Setting 1: Parameter changes applied immediately and saved in drive on Enter command input
Parameter changes are applied as soon as they are made. The parameter changes are saved to EEPROM in the drive when
an Enter command with 0900H set to 0 is input.
H5-12: Run Command Method Selection
Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications (b1-02,
b1-16 = 2).
Setting 0: FWD/Stop, REV/Stop
Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive in the forward direction. Setting bit 1
will start and stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV
Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive. Setting bit 1 changes the direction.
H5-17: Operation Selection when Unable to Write into EEPROM
There is normally no need to change this parameter from the default value.
Selects the operation to be carried out
when an attempt is made to write data into EEPROM by MEMOBUS/Modbus
communications if writing into EEPROM is not enabled.
Setting 0: Cannot write into EEPROM.
Setting 1: Write in RAM only.
H5-18: Filter Time Constant for Motor Speed Monitoring
Sets the filter time constant for monitoring the motor speed from MEMOBUS/Modbus communications and
communication option.
Applicable MEMOBUS/Modbus registers
: 3EH, 3FH, 44H, ACH, and ADH
Note: This parameter is not available in models CIMR-A4A0930 and 4A1200.
No. Name Setting Range Default
H5-11 Communications Enter Function Selection 0 or 1 0
No. Name Setting Range Default
H5-12 Run Command Method Selection 0 or 1 0
No. Name Setting Range Default
H5-17 Operation Selection when Unable to Write into EEPROM 0, 1 0
No. Name Setting Range Default
H5-18 Filter Time Constant for Motor Speed Monitoring 0 to 100 ms 0 ms

Table of Contents

Other manuals for YASKAWA A1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 and is the answer not in the manual?

YASKAWA A1000 Specifications

General IconGeneral
TypeAC Drive
SeriesA1000
Input Voltage200-240V, 380-480V
Frequency Range0-400 Hz
Horsepower Range0.5 to 1000 HP
Power Range0.4 to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
BrakingDynamic Braking
CommunicationModbus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Operating Temperature-10 to +50°C
Storage Temperature-20 to 60°C
Humidity5 to 95% RH (non-condensing)
EnclosureIP20

Related product manuals