3.8 Main Circuit Wiring
78 YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Note: When connecting peripheral devices and options to the terminals –, +1, +3, B1, and B2, refer to the instruction manuals for each
devices. For more information, contact YASKAWA or your nearest sales representative.
2A0169
R/L1, S/L2, T/L3 70 50 to 95
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 70 50 to 95
–, +1 – 35 to 95
+3 – 50 to 95
35 25 to 35
2A0211
R/L1, S/L2, T/L3 95 70 to 95
M10
18 to 23
(15
9 to 204)
U/T1, V/T2, W/T3 95 70 to 95
–, +1 – 35 to 95
+3 – 50 to 95
50 25 to 50
2A0250
R/L1, S/L2, T/L3 95 2P 95 to 150
M12
32 to 40
(28
3 to 354)
U/T1, V/T2, W/T3 95 2P 95 to 150
–, +1 – 70 to 150
+3 – 35 to 150 M10
18 to 23
(15
9 to 204)
95 95 to 150 M12
32 to 40
(283 to 354)
2A0312
R/L1, S/L2, T/L3 95 2P 95 to 150
M12
32 to 40
(28
3 to 354)
U/T1, V/T2, W/T3 95 2P 95 to 150
–, +1 – 70 to 150
+3 – 70 to 150 M10
18 to 23
(15
9 to 204)
95 95 to 150 M12
32 to 40
(283 to 354)
2A0360
R/L1, S/L2, T/L3 240 95 to 300
M12
32 to 40
(28
3 to 354)
U/T1, V/T2, W/T3 240 95 to 300
–, +1 – 125 to 300
+3 – 70 to 300 M10
18 to 23
(15
9 to 204)
120 120 to 240 M12
32 to 40
(283 to 354)
2A0415
R/L1, S/L2, T/L3 120 2P 95 to 300
M12
32 to 40
(28
3 to 354)
U/T1, V/T2, W/T3 300 95 to 300
–, +1 – 150 to 300
+3 – 70 to 300 M10
18 to 23
(15
9 to 204)
120 120 to 240 M12
32 to 40
(28
3 to 354)
<1> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an equipment for residual current monitoring/detection
(RCM/RCD).
<2> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an equipment for residual current monitoring/detection
(RCM/RCD), or use copper wire of 10 mm
2
(AWG 8).
Model
CIMR-A
Terminal
Recomm. Gauge
mm
2
Applicable
Gauge
mm
2
Screw
Size
Tightening
Torque
Nm (lb.in.)