Maintenance-Object Repair Procedures
555-233-143
8-446 Issue 1 May 2002
0NO
BOARD
The test could not relate the internal ID to the port (no board).
This result could be due to incorrect translations, no board is inserted, an
incorrect board is inserted, an insane board is inserted, or the board is
hyperactive.
1. Verify that the board’s translations are correct. Use the list config
command, and resolve any problems that are found.
2. If the board was found to be correctly inserted in step 1, issue the busyout
board command.
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board long command.
This should re-establish the linkage between the internal ID and the port. If
not, dispatch to verify that a valid board is inserted.
NOTE:
Hyperactivity causes some special problems with the sequence
suggested above.If the ports are translated after issuing the list config
command but the
Vintage field reports that there is no board (when
there really is a board), then the busyout board and the release busy
board commands will not work (even though the reset board command
will work). The software will put the hyperactive board back in service
after the hyperactivity clears.
Table 8-180. Test #7 Conference Circuit Test — Continued
Error
Code
Tes t
Result Description / Recommendation
Continued on next page