Maintenance Commands
555-233-143
7-242 Issue 1 May 2002
recycle carrier
recycle carrier UUC
NOTE:
This command is not valid for S8700 IP Connect configurations.
The recycle carrier command turns power off, then back on, on a specific carrier.
When a power unit is replaced in a carrier, this command must be entered to
restart the power on that carrier. The following carriers cannot be recycled:
■ Switch Node Carrier
■ PN Control Carrier
■ Any carrier holding an active Tone-Clock or an active EI circuit pack
!
CAUTION:
When a port carrier is recycled, every port and adjunct supported by circuit
packs on that carrier undergoes a service outage.
!
CAUTION:
Never recycle power to a carrier containing DEFINITY AUDIX
TN566/TN2169 circuit packs without first shutting down the AUDIX system.
Doing so can damage AUDIX software. Follow instructions on the
TN566/TN2169 faceplate (these also appear under ADXDP-PT in
Chapter 8, ‘‘Maintenance-Object Repair Procedures’’).
On G3r V1 systems, the TN566/TN2169 may appear as a TN746 with a
vintage greater than 50.
For more information, see the following sections: ‘‘Common Input Parameters’’
on page 7-6 and ‘‘Common Output Fields’’ on page 7-9.