Maintenance-Object Repair Procedures
555-233-143
8-682 Issue 1 May 2002
Failure Audit (#949)
This test is nondestructive.
This test queries the DS1 CONV circuit pack for any existing circuit pack or facility
failures and any unacknowledged cleared failure messages. Upon receiving the
query request, DS1 CONV firmware sends failure reports to the maintenance
software for every error in its failure database.
This test operates on both MOs DS1C-BD and DS1-FAC. Error counts of both
MOs (DS1C-BD and DS1-FAC) that are displayed in the error log will be
incremented when this test is executed. This test is executed via the test board
command. The test is also executed internally by the maintenance software when
an alarm is resolved
Table 8-267. Test #949 Failure Audit
Error
Code
Tes t
Result Description / Recommendation
2100 ABORT Could not allocate the necessary system resources to run this test.
2000 ABORT Timed out while waiting for a response from the circuit pack.
2300 ABORT The downlink message necessary to run this test could not be sent.
2301 ABORT The timer could not be set before sending the downlink message necessary to
run this test.
1. Retry the command at 1-minute intervals up to 3 times.
2316 ABORT Fiber link is not administered. Administer the DS1 CONV fiber link via the add
fiber-link command.
2500 ABORT Internal system error
1. Retry the command at 1-minute intervals up to 3 times.
FAIL The DS1 CONV circuit pack reported failures or retransmitted a cleared failure
message.
1. Enter display errors and follow the associated repair procedures for any
DS1C-BD and DS1-FAC errors.
PASS The DS1 CONV circuit pack has no failures.