Maintenance-Object Repair Procedures
555-233-143
8-706 Issue 1 May 2002
Reset Test (#787)
This test is destructive.
DS1 CONV circuit pack is reset via the reset board command. When the circuit
pack is reset, firmware executes a series of diagnostic tests on the circuit pack.
The results of these tests are queried from the board when the board is inserted
after completion of the reset sequence. If any of the diagnostic tests fail, the error
log will have an entry of Error Type #1 for this circuit pack’s location, and the alarm
log will have an entry of ON-BOARD MAJOR alarm.
The reset sequence will take about one minute to complete.
Table 8-273. Test #787 Reset Board
Error
Code
Tes t
Result Description / Recommendation
2100 ABORT Could not allocate the necessary system resources to run this test.
2300 ABORT The downlink message necessary to run this test could not be sent.
2301 ABORT The timer could not be set before sending the downlink message necessary to
run this test.
1. Retry the command at 1-minute intervals up to 3 times.
2316 ABORT Fiber link is not administered. Administer the DS1 CONV fiber link via the add
fiber-link command.
2321 ABORT DS1 CONV circuit pack is not busied out. Busyout the DS1 CONV circuit pack
via the busyout board command.
2500 ABORT Internal system error
1. Retry the command at 1-minute intervals up to 3 times.
PASS Reset sequence was executed successfully. (However, this test result does
not indicate whether the firmware diagnostic tests passed.)
1. Enter the display errors command to check the error log for any failed
diagnostic firmware tests. (This is indicated by an entry of Error Type #1
for this circuit pack’s location.)
2. Enter the display alarms command to check the alarm log for any
ON-BOARD MAJOR alarms.
0NO
BOARD
The system software found no board.
1. Reset the board.
2. Remotely retry the command.