Maintenance-Object Repair Procedures
555-233-143
8-866 Issue 1 May 2002
146 FAIL The SNI circuit pack (Endpoint 1 of the fiber link) has a fiber out-of-frame
condition, and a loss-of-signal condition. Also, no lightwave transceiver is
connected to the SNI circuit pack.
1. Check that the connected circuit pack is physically installed. The
connected circuit pack is the other endpoint of the fiber link if no DS1
CONV complex is administered (check via list fiber-link). Otherwise, if a
DS1 CONV complex is administered, the connected circuit pack is the DS1
CONV circuit pack connected to the SNI circuit pack.
2. Perform the ‘‘Fault Isolation for Fiber Links’’ on page 4-19 in Chapter 5.
3. Replace this SNI circuit pack.
4. Replace the connected circuit pack.
241 FAIL The SNI circuit pack (Endpoint 2 of the fiber link) has a fiber out-of-frame
condition, but no loss-of-signal condition. Also, a lightwave transceiver is
connected to the SNI circuit pack.
1. Check that the connected circuit pack is physically installed. The
connected circuit pack is the other endpoint of the fiber link if no DS1
CONV complex is administered (check via list fiber-link). Otherwise, if a
DS1 CONV complex is administered, the connected circuit pack is the DS1
CONV circuit pack connected to the SNI circuit pack.
2. Perform the ‘‘Fault Isolation for Fiber Links’’ on page 4-19 in Chapter 5.
3. Replace this SNI circuit pack.
4. Replace the connected circuit pack.
242 FAIL The SNI circuit pack (Endpoint 2 of the fiber link) has a fiber out-of-frame
condition, but no loss-of-signal condition. Also, no lightwave transceiver is
connected to the SNI circuit pack.
1. Check that the connected circuit pack is physically installed. The
connected circuit pack is the other endpoint of the fiber link if no DS1
CONV complex is administered (check via list fiber-link). Otherwise, if a
DS1 CONV complex is administered, the connected circuit pack is the DS1
CONV circuit pack connected to the SNI circuit pack.
2. Perform the ‘‘Fault Isolation for Fiber Links’’ on page 4-19 in Chapter 5.
3. Replace this SNI circuit pack.
4. Replace the connected circuit pack.
Table 8-331. Test #989 SNI Fiber Out of Frame Query Continued
Error
Code
Tes t
Result Description / Recommendation
Continued on next page